00:00:00.560 --> 00:00:02.112
Ground Truth, for technicians.

2
00:00:02.112 --> 00:00:04.795
Where the signals live,
and how to troubleshoot.

3
00:00:05.205 --> 00:00:06.795
Inside CP-101:

4
00:00:06.795 --> 00:00:12.776
a MicroLogix controller, two level
trip amplifiers, and relays K1 to K5.

5
00:00:12.894 --> 00:00:17.399
The input and output lights and
every relay follow the live logic.

6
00:00:17.399 --> 00:00:20.335
K1 and K2 carry the pump permissives.

7
00:00:20.335 --> 00:00:24.835
K5 is the LY-V110 trip relay,
energized when healthy.

8
00:00:24.978 --> 00:00:29.444
The two output fuse carriers for the horn
and the common alarm were found open.

9
00:00:29.663 --> 00:00:35.390
The external trip from X130 arrives as a
DC signal, through a solid-state relay,

10
00:00:35.390 --> 00:00:36.234
SSR1.

11
00:00:38.635 --> 00:00:41.303
On the I/O tab, every
signal has its terminal,

12
00:00:41.303 --> 00:00:45.679
its live value in the controller and
in the field, and a force selector.

13
00:00:46.491 --> 00:00:47.833
Now the important one.

14
00:00:47.833 --> 00:00:51.006
These trip inputs only trip
when they are energized.

15
00:00:51.006 --> 00:00:56.132
We open the wire to the LY-X130
input, and then X130 sends a trip.

16
00:00:56.182 --> 00:00:57.178
Nothing happens.

17
00:00:57.178 --> 00:00:58.609
The pump keeps running.

18
00:00:58.609 --> 00:01:03.476
To the controller, a broken wire looks
exactly like a healthy, quiet input.

19
00:01:04.722 --> 00:01:07.009
Restore the wire, and the trip goes through:

20
00:01:07.009 --> 00:01:09.392
the pump trip latches, and the pump stops.

21
00:01:11.822 --> 00:01:14.569
The event log lists every
change in scan order:

22
00:01:14.569 --> 00:01:17.843
the input first, then the
latches and outputs it caused.

23
00:01:17.843 --> 00:01:19.972
Start there when something trips.

24
00:01:20.913 --> 00:01:23.584
An open wire on a trip input gives no trip.

25
00:01:23.584 --> 00:01:25.585
Prove every trip, end to end.